Rơ le bảo vệ pha Omron K8AB-PH1-L 200/500VAC
Input voltage range | 200 to 500 VAC |
Input frequency range | 45 to 65 Hz |
Overload capacity | Continuous input: 115% of maximum input, 10 s max.: 125% of maximum input |
Fixed Phase Asymmetry | Output relay releases when one phase-phase voltage drops below 80% of the other |
Monitoring | phase-phase voltage. |
Temperature influence | Operating time |
Fluctuation based on measured value at standard temperature: | |
-20°C to standard temperature: ±10% max. | |
Standard temperature to 60°C: ±10% max. | |
(Humidity: 25% to 80%) | |
Humidity influence | Operating time |
Based on ambient room humidity | |
25% to 80%: ±10% max. | |
Influence of power supply | Operating time: ±10% max. |
voltage | Note: The error in the operating value and operating time under standard conditions. |
Influence of power supply | Operating time: ±10% max. (at 45 to 65 Hz) |
frequency | Note: The error in the operating value and operating time under standard conditions. |
Influence of input | At 45 to 65 Hz |
frequency | Operating time: ±10% max. |
Note: The error in the operating value and operating time under standard conditions. | |
Insulation resistance | 20 MΩ min. |
Between external terminals and case | |
Between input terminals and output terminals | |
Dielectric strength | 2,000 VAC for one minute |
Between external terminals and case | |
Between input terminals and output terminals | |
Noise immunity | 1,500 V power supply terminal common/normal mode |
Square-wave noise of ±1 μs/100 ns pulse width with 1-ns rise time | |
Vibration resistance | Frequency 10 to 55 Hz, 0.35-mm single amplitude, acceleration 50 m/s2 |
10 sweeps of 5 min each in X, Y, and Z directions | |
Shock resistance | 100 m/s2, 3 times each in 6 directions along three axes (up/down, left/right, forward/ |
backward) | |
Degree of protection | Terminal section: Finger protection |
Thông tin bổ sung
Thương hiệu |
Omron |
---|---|
Thời gian bảo hành |
1 Năm |
Điện áp điều khiển |
220V, 380V |
Loại |
Rơ le bảo vệ pha |